MECHATROLINK Transmission Specifications
MECHATROLINK
Function Specification MECHATROLINK-II MECHATROLINK-III
Physical Layer Equivalent to RS-485 Ethernet
Baud Rate 10 Mbps 100 Mbps
Transmission Cycle Time 250 µs to 8 ms* 31.25 µs to 64 ms*
String Size 17 bytes or 32 bytes
(Both string sizes cannot be used at the same time)
8/16/32/48/64 bytes (Different string sizes can be used as the same time)
Number of Slaves 30 max. 62 max.
Maximum Transmission Distance 50 m total
(100 m with Repeater)
100 m between stations 0.5 m
Minimum Distance between Stations 0.5 m 0.2 m
Topology Bus Cascade, star,
or point-to-point
Cyclic/Event-driven Communications Cyclic communications possible Cyclic and event-driven communications supported.
Message Communications None Available